PERMALOK
CORPORATION
472 Paul Avenue
St. Louis, MO 63135
October 22, 2002
Lab No. 02P-1946
Attention: Dave Mittler
Report of Analysis
SAMPLE ID:
#5-30” Permalok
Connector Joining System
SUBJECT:
Hydrostatic Pressure Testing
TESTING SITE:
B & D Metals Products, 5980
St. Louis Avenue
PROCEDURE:
Testing blinds were attached to a shortened length of the
connector assembly and placed into the test fixture. Prior
to assembly and installation both male and female couplings
were visually examined for proper tolerances, joint type and
fit up. The coupling halves were then pressed together using
the necessary jacks, shims and clamping fixtures. Figure 1
illustrates the typical set up and configuration of the fitted
30” Permalok Connector.
The sealed unit was then hydrostatic pressure tested with
potable water to a pressure of 90 psi and held for 30 minutes.
The pressure was then increased to 150 psi and held for an
additional 15 minutes.
RESULTS:
No deformation or drop in pressure was noted during the testing
of the above identified connector assembly.
KS/kss
Karl Schmitz, Director
Materials Testing
St. Louis Testing Laboratories, Inc.
2810 Clark Avenue
St. Louis, MO